Main Characteristics
2.1. Equipped with a three-phase standard meter, which can carry out error test and word run test; or
Take the leader table as the benchmark, and carry out the word-walking test.
2.2, a variety of structural forms, divided into two forms of one body and one body.
2.3. Aluminium alloy meter hanging rack; two-sided hanging meter, one side hanging 24 pieces of single-phase electric energy
The other side hangs 12 three-phase electric energy meters.
2.4. Separate wiring for word run and withstand voltage test, which has the characteristics of safety and reliability.
point.
2.5. The function switch of moving word and withstand voltage has interlock function, and can only perform one
Test, with the characteristics of safety and reliability.
2.6. Characters of the character part:
♦ Each table position is equipped with multi-function signal input interface, one-time wiring,
According to the regulations, one inspection is completed.
♦ Each table position is equipped with a 6-digit multi-function display box, which can display the number of word pulses
( 0~999999 ).
♦ The word power source adopts PWM power amplifier, which has the advantages of high output power and heat generation.
Small, low failure rate and so on.
♦ Each table position is equipped with 485 communication interface, which is convenient to carry out multi-function word running test.
♦Single-phase and three-phase running word test are switched by interlock switch.
♦ The result of the word movement can be uploaded and printed through the management software for data management.
(optional function)
2.7. Features of withstand voltage:
♦ Install safety protection equipment on both sides of the watch rack.
The protective light curtain is activated, which is safe and convenient.
♦ During the withstand voltage test, each epitope has a sound and light alarm, when a certain epitope hits
When worn, there is a status indicator light next to the table position, indicating the fault table position, and concurrent
An alarm sounds. The fault epitope automatically disconnects the high voltage and will not affect other epitope tests.
♦ The results of the withstand voltage test can be saved and uploaded through a PC.
Function. (optional)
♦ A warning light is set on the top of the device, when the withstand voltage test, the three-color warning lights up
light O
♦ Withstand voltage tester adopts PWM power amplifier technology, with automatic and manual functions;
Technical Indicators
Parameter name (SYH12 pressure tester) | main indicators | |
---|---|---|
Output voltage range | three phase | 3x57.7V, 100V, 220V, 380V |
Simplex | 220V | |
Adjust fineness | 10%, 1%, 0.1% | |
Output current range | single, three-phase | 3x1.5A, 2.5A, 5A, 10A, 20A, 30A |
Adjust fineness | 10%, 1%, 0.1% | |
Output voltage, current distortion | ≤1% | |
Output frequency | 50Hz/60Hz | |
Voltage, current, power output stability | 0.1% | |
Output Power | Voltage≤500VA/phase Current≤800VA/phase | |
Pulse count range | 0~999999 | |
Voltage, current, power factor, phase, frequency display accuracy | 0.2% | |
input power | 220V ±10%, maximum power consumption: 2000VA |
Shape Indicators
parameter name | Main indicators (length × depth × height) | |
---|---|---|
Split | source | 600×800×1920 mm3 |
watch rack | 2150×800×1820 mm3 | |
one | 2350×800×1820 |